Installation and Connection
3.2 Good EMC Installation Techniques
1) Mount the COMBIVERT F5 on a conductive
(zinc or nickel plated not painted) subpanel.
This sub plate serves as the central grounding
point for the machine.
2) Always connect the shield of motor and
control cables with maximum surface area,
use a metal cable clamp to contact cable
shield on all sides. Using a single strand of
the shield or the drain wire from the shield
as the only connection can reduce the
shield’s effectiveness by 70%.
3) The distance between control and power
cables should be at least 10..20 cm / 4...8
inches.
4) Keep the motor and power cable spatially
separated especially if running parallel.
5) If it cannot be avoided, cross control and
power cables and motor cables at a right
angle.
6) Install all cables as close as possible to the
mounting plate - ideally in a metal wireway.
7) Ridged metal conduit can be used as a
shield for the motor cables. Always observe
the following points:
• Remove all paint from the control panel where the conduit is to be secured.
• Securely fasten all conduit fittings.
• Run only the motor wires through the conduit. All other wires must be pulled
through a separate conduit.
• Connect the control panel to the sub panel with a heavy ground strap.
8) If a KEB EMI (CE) filter is used, it must be mounted as close as possible and to the
same subpanel as the COMBIVERT F5 motor control. The filter must have large bare
surface contact with the subpanel. Use only the wires from the filter to connect to the
inverter. Never add additional lengths of wire.
9) All ground connections should be as short as possible. Always avoid creating ground
loops. NEC requires a ground conductor connected to every COMBIVERT F5 controller
in spite of the metal on metal connection to the subpanel.
You can find further instructions regarding EMC and proper wiring considerations by
contacting KEB technical support or visiting the web site www.kebamerica.com.
90°
10-20cm
4...8 in
4
5
1
6
6
3
2
2